Tello-Oquendo, F.; Navarro-Peris, E.; Barceló Ruescas, F.; Gonzálvez-Maciá, J. (2019). Semi-empirical model of scroll compressors and its extension to describe vapor-injection compressors. Model description and experimental validation. International Journal of Refrigeration. 106:308-326. https://doi.org/10.1016/j.ijrefrig.2019.06.031
Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/10251/141955
Título:
|
Semi-empirical model of scroll compressors and its extension to describe vapor-injection compressors. Model description and experimental validation
|
Otro titulo:
|
Modélisation semi-empirique de compresseurs à spirale et ses extensions pour décrire les compresseurs à injection de vapeur. Description du modèle et la validation expérimentale
|
Autor:
|
Tello-Oquendo, Fernando
Navarro-Peris, Emilio
Barceló Ruescas, Francisco
Gonzálvez-Maciá, José
|
Entidad UPV:
|
Universitat Politècnica de València. Instituto de Ingeniería Energética - Institut d'Enginyeria Energètica
Universitat Politècnica de València. Departamento de Termodinámica Aplicada - Departament de Termodinàmica Aplicada
|
Fecha difusión:
|
|
Resumen:
|
[EN] This paper presents a semi-empirical model of scroll compressors and proposes a methodology in order to extend this model to vapor-injection scroll compressors. The model takes into account the ideal evolution of the ...[+]
[EN] This paper presents a semi-empirical model of scroll compressors and proposes a methodology in order to extend this model to vapor-injection scroll compressors. The model takes into account the ideal evolution of the refrigerant throughout the compressor and considers the main sources of losses in the compression process. The model is able to predict the compressor and volumetric efficiencies in terms of ten empirical parameters, which have a direct physical interpretation. For the model validation, a series of four non-injected scroll compressors of different capacities were tested using R-290 and a scroll compressor with vapor-injection (SCVI) was characterized using R-407C. Results show a correct agreement between the experimental and calculated compressor efficiencies, with a maximum deviation of ±5%. Furthermore, the model estimates accurately the discharge temperature of the refrigerant, compressor power input, and refrigerant mass flow rate in the suction and injection port. Finally, the SCVI model response was evaluated by varying the intermediate pressure and the injection superheat.
[-]
|
Palabras clave:
|
Scroll compressor
,
Semi-empirical model
,
Vapor-injection
,
Experimental validation
,
Compresseur à spirale
,
Modèle semi-empirique
,
Injection de vapeur
,
Validation expérimentale
|
Derechos de uso:
|
Reserva de todos los derechos
|
Fuente:
|
International Journal of Refrigeration. (issn:
0140-7007
)
|
DOI:
|
10.1016/j.ijrefrig.2019.06.031
|
Editorial:
|
Elsevier
|
Versión del editor:
|
https://doi.org/10.1016/j.ijrefrig.2019.06.031
|
Código del Proyecto:
|
info:eu-repo/grantAgreement/SENESCYT//2015-AR37665/
info:eu-repo/grantAgreement/AEI/Plan Estatal de Investigación Científica y Técnica y de Innovación 2013-2016/ENE2017-83665-C2-1-P/ES/MAXIMIZACION DE LA EFICIENCIA Y MINIMIZACION DEL IMPACTO AMBIENTAL DE BOMBAS DE CALOR PARA LA DESCARBONIZACION DE LA CALEFACCION%2FACS EN LOS EDIFICIOS DE CONSUMO CASI NULO/
|
Agradecimientos:
|
Fernando M. Tello-Oquendo acknowledges the financial support provided by the CONVOCATORIA ABIERTA 2013-SEGUNDA FASE program, which was funded by the SENESCYT (Secretaría de Educación Superior, Ciencia, Tecnología e Innovación) ...[+]
Fernando M. Tello-Oquendo acknowledges the financial support provided by the CONVOCATORIA ABIERTA 2013-SEGUNDA FASE program, which was funded by the SENESCYT (Secretaría de Educación Superior, Ciencia, Tecnología e Innovación) (Grant No 2015-AR37665) of Ecuador. The authors would like to acknowledge the Spanish MINISTERIO DE ECONOMIA Y COMPETITIVIDAD , through the project ref-ENE2017-83665-C2-1-P Maximización de la eficiencia y minimización del impacto ambiental de bombas de calor para la descarbonización de la calefacción/ACS en los edificios de consumo casi nulo for the given support.
[-]
|
Tipo:
|
Artículo
|