Corberán, JM.; D.Donadello; Martínez Galván, IO.; Montagud, C. (2013). Partialization losses of ON/OFF operation of waterto- water refrigeration/heat-pump units. International Journal of Refrigeration. 36(8):2251-2261. https://doi.org/10.1016/j.ijrefrig.2013.07.002
Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/10251/47516
Title:
|
Partialization losses of ON/OFF operation of waterto- water refrigeration/heat-pump units
|
Author:
|
Corberán, José M.
D.Donadello
Martínez Galván, Israel Octavio
Montagud, C.
|
UPV Unit:
|
Universitat Politècnica de València. Departamento de Termodinámica Aplicada - Departament de Termodinàmica Aplicada
Universitat Politècnica de València. Instituto de Ingeniería Energética - Institut d'Enginyeria Energètica
|
Issued date:
|
|
Abstract:
|
[EN] This paper presents the results of an experimental campaign for the characterization of the dynamic behavior of a water-to-water refrigeration/heat-pump unit under ON/OFF operation.
The unit was previously tested at ...[+]
[EN] This paper presents the results of an experimental campaign for the characterization of the dynamic behavior of a water-to-water refrigeration/heat-pump unit under ON/OFF operation.
The unit was previously tested at different water inlet temperatures under steady
state conditions, and a very good agreement was found between the instantaneous dynamic performance of the heat pump and the corresponding quasi-steady state operation.
In parallel, a series of tests were carried out to quantify the coefficient of performance
(COP) degradation as a function of the load ratio, and a simple formula for the Part Load
Factor is presented. Results lead to the conclusion that the only non-negligible factor in the COP degradation is the stand-by electrical consumption during the OFF period, especially at low load ratios. Finally, it is concluded that the minimization of the stand-by consumption is a key point for the future improvement of the seasonal performance of water-to-water systems.
[-]
|
Subjects:
|
Part load operation
,
Heat pump performance
,
Partialization losses
,
COP
|
Copyrigths:
|
Reserva de todos los derechos
|
Source:
|
International Journal of Refrigeration. (issn:
0140-7007
)
|
DOI:
|
10.1016/j.ijrefrig.2013.07.002
|
Publisher:
|
Elsevier
|
Publisher version:
|
http://dx.doi.org/10.1016/j.ijrefrig.2013.07.002
|
Project ID:
|
info:eu-repo/grantAgreement/MICINN//DPI2011-26771-C02-01/ES/ESTUDIO DE EVAPORADORES Y CONDENSADORES BASADOS EN TECNOLOGIA DE MINICANALES PARA SU APLICACION EN EQUIPOS DE AIRE ACONDICIONADO, REFRIGERACION Y BOMBA DE CALOR ESTACIONARIOS/
info:eu-repo/grantAgreement/EC/FP7/218895/EU/Advanced ground source heat pump systems for heating and cooling in Mediterranean climate/
|
Thanks:
|
This research has been partially funded by the European FP7 framework project "Advanced ground source heat pump systems for heating and cooling in Mediterranean climate" (GROUND-MED) and the Spanish Ministry of Economy and ...[+]
This research has been partially funded by the European FP7 framework project "Advanced ground source heat pump systems for heating and cooling in Mediterranean climate" (GROUND-MED) and the Spanish Ministry of Economy and Competitiveness (MINECO) through the project "Estudio de evaporadores y condensadores basados en tecnologia de minicanales para su aplicaciOn en equipos de aire acondicionado, refrigeraciOn y bomba de calor estacionarios" with reference DPI2011-26771-C02-01. The authors gratefully acknowledge their financial support.
[-]
|
Type:
|
Artículo
|