Mostrar el registro sencillo del ítem
dc.contributor.author | Mota Babiloni, Adrián | es_ES |
dc.contributor.author | Navarro Esbri, Joaquin | es_ES |
dc.contributor.author | Barragán Cervera, Ángel | es_ES |
dc.contributor.author | Moles Ribera, Francisco | es_ES |
dc.contributor.author | Peris Pérez, Bernardo | es_ES |
dc.date.accessioned | 2015-12-15T12:48:46Z | |
dc.date.available | 2015-12-15T12:48:46Z | |
dc.date.issued | 2014-08 | |
dc.identifier.issn | 0140-7007 | |
dc.identifier.uri | http://hdl.handle.net/10251/58842 | |
dc.description.abstract | Six refrigerants are evaluated as low GWP replacements for R404A using different configurations, including two-stage system architectures. These refrigerants are selected according to similar characteristics to R404A, and they are the mid-term alternatives R407A and R407F, and the long-term alternatives: L40 and DR-7 (with very low GWP and low flammability), N40 and DR-33 (with low GWP and no flammability). In order to have a complete comparison range, various operating conditions are considered, covering low and medium evaporator temperatures and two levels of condensation temperatures. Configurations selected are presented and the equations used to simulate the expected performance are shown. From a given cooling capacity, volumetric flow rate and COP are compared, taking R404A as baseline. The most efficient alternatives are the low-flammable refrigerants, L40 and DR-7, and when no flammability is acceptable, N40 and DR-33 are also very good options. | es_ES |
dc.description.sponsorship | The authors thankfully acknowledge "Ministerio de Educacion, Cultura y Deporte" for supporting this work through "Becas y Contratos de Formacion de Profesorado Universitario del Programa Nacional de Formacion de Recursos Humanos de Investigacion del ejercicio 2012" The authors also want to acknowledge Honeywell International Inc. for supporting this work. | en_EN |
dc.language | Inglés | es_ES |
dc.publisher | Elsevier | es_ES |
dc.relation.ispartof | International Journal of Refrigeration | es_ES |
dc.rights | Reserva de todos los derechos | es_ES |
dc.subject | Refrigeration | es_ES |
dc.subject | Configurations | es_ES |
dc.subject | R404A replacement | es_ES |
dc.subject | GWP: Coefficient of Performance | es_ES |
dc.title | Theoretical comparison of low GWP alternatives for different refrigeration configurations taking R404A as baseline | es_ES |
dc.title.alternative | Comparaison the´orique des alternatives a` faible GWP pour diverses configurations frigorifiques prenant le R404A comme point de re´fe´ rence | es_ES |
dc.type | Artículo | es_ES |
dc.identifier.doi | 10.1016/j.ijrefrig.2014.04.015 | |
dc.rights.accessRights | Abierto | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Departamento de Termodinámica Aplicada - Departament de Termodinàmica Aplicada | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Instituto de Seguridad Industrial, Radiofísica y Medioambiental - Institut de Seguretat Industrial, Radiofísica i Mediambiental | es_ES |
dc.description.bibliographicCitation | Mota Babiloni, A.; Navarro Esbri, J.; Barragán Cervera, Á.; Moles Ribera, F.; Peris Pérez, B. (2014). Theoretical comparison of low GWP alternatives for different refrigeration configurations taking R404A as baseline. International Journal of Refrigeration. 44:81-90. doi:10.1016/j.ijrefrig.2014.04.015 | es_ES |
dc.description.accrualMethod | S | es_ES |
dc.relation.publisherversion | http://dx.doi.org/10.1016/j.ijrefrig.2014.04.015 | es_ES |
dc.description.upvformatpinicio | 81 | es_ES |
dc.description.upvformatpfin | 90 | es_ES |
dc.type.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.description.volume | 44 | es_ES |
dc.relation.senia | 268167 | es_ES |
dc.contributor.funder | Ministerio de Educación, Cultura y Deporte | es_ES |