Impact of electromagnetic losses in closed two-component magnetic shields on the thermal ampacity of underground power cables

RiuNet: Repositorio Institucional de la Universidad Politécnica de Valencia

Compartir/Enviar a

Citas

Estadísticas

  • Estadisticas de Uso

Impact of electromagnetic losses in closed two-component magnetic shields on the thermal ampacity of underground power cables

Mostrar el registro sencillo del ítem

Ficheros en el ítem

dc.contributor.author Pino López, Juan Carlos del es_ES
dc.contributor.author Cruz Romero, Pedro es_ES
dc.contributor.author Serrano Iribarnegaray, Luís es_ES
dc.date.accessioned 2016-05-05T12:02:01Z
dc.date.available 2016-05-05T12:02:01Z
dc.date.issued 2013
dc.identifier.issn 1559-8985
dc.identifier.uri http://hdl.handle.net/10251/63703
dc.description.abstract In this paper two typical arrangements of underground single-core high voltage three-phase power cables (flat and trefoil protected by PVC pipes) inside a closed shield of three different materials (low-carbon steel, non-oriented grain steel and aluminium) are analysed. The shield has two components: a U-shaped base and a flat plate (cover) located on top of the base. Whereas most of previous papers on this subject only dealt with the degree of mitigation obtained with each material, this paper, in addition to also addressing this issue, mainly focusses on the effect that electromagnetic losses induced in the shield have on the ampacity of the cable and the cost involved (material and losses). To obtain the numerical results, a high number of simulations by a well-known commercial finite element method software (COMSOL Multiphysics) have been performed. The results obtained in the numerous cases analysed are widely commented and the solutions that enable an important mitigation with no current derating and at a comparatively low cost are highlighted. es_ES
dc.description.sponsorship This work has been supported by the Spanish Ministry of Science & Innovation under grant ENE2010-18867 and by the regional Government of Andalucia under grant P09-TEP-5170. en_EN
dc.language Inglés es_ES
dc.publisher EMW Publishing es_ES
dc.relation.ispartof Progress In Electromagnetics Research es_ES
dc.rights Reserva de todos los derechos es_ES
dc.subject Electromagnetic losses es_ES
dc.subject Cables ampacity es_ES
dc.subject underground cables es_ES
dc.subject magnetic shields es_ES
dc.title Impact of electromagnetic losses in closed two-component magnetic shields on the thermal ampacity of underground power cables es_ES
dc.type Artículo es_ES
dc.identifier.doi 10.2528/PIER12112303
dc.relation.projectID info:eu-repo/grantAgreement/MICINN//ENE2010-18867/ES/ESTIMACION DE ESTADO DINAMICA EN REDES ELECTRICAS. IMPLEMENTACION DISTRIBUIDA EN ARQUITECTURAS MULTINIVEL./ es_ES
dc.relation.projectID info:eu-repo/grantAgreement/Junta de Andalucía//P09-TEP-5170/ES/Optimización Y Control De Sistemas De Energías Renovables Para Mejorar Su Integración En La Red Eléctrica Andaluza/ es_ES
dc.rights.accessRights Abierto es_ES
dc.contributor.affiliation Universitat Politècnica de València. Departamento de Ingeniería Eléctrica - Departament d'Enginyeria Elèctrica es_ES
dc.description.bibliographicCitation Pino López, JCD.; Cruz Romero, P.; Serrano Iribarnegaray, L. (2013). Impact of electromagnetic losses in closed two-component magnetic shields on the thermal ampacity of underground power cables. Progress In Electromagnetics Research. 135:601-625. https://doi.org/10.2528/PIER12112303 es_ES
dc.description.accrualMethod S es_ES
dc.relation.publisherversion http://dx.doi.org/10.2528/PIER12112303 es_ES
dc.description.upvformatpinicio 601 es_ES
dc.description.upvformatpfin 625 es_ES
dc.type.version info:eu-repo/semantics/publishedVersion es_ES
dc.description.volume 135 es_ES
dc.relation.senia 257631 es_ES
dc.contributor.funder Junta de Andalucía es_ES
dc.contributor.funder Ministerio de Ciencia e Innovación es_ES


Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem