Alfonso Gil, JC.; Orts-Grau, S.; Muñoz Galeano, N.; Gimeno Sales, FJ.; Segui-Chilet, S. (2013). Measurement system for a power quality improvement structure based on IEEE Std.1459. IEEE Transactions on Instrumentation and Measurement. 62(12):3177-3188. https://doi.org/10.1109/TIM.2013.2270901
Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/10251/78004
Title:
|
Measurement system for a power quality improvement structure based on IEEE Std.1459
|
Author:
|
Alfonso Gil, José Carlos
Orts-Grau, Salvador
Muñoz Galeano, Nicolás
Gimeno Sales, Francisco José
Segui-Chilet, Salvador
|
UPV Unit:
|
Universitat Politècnica de València. Escuela Técnica Superior de Ingeniería del Diseño - Escola Tècnica Superior d'Enginyeria del Disseny
Universitat Politècnica de València. Departamento de Ingeniería Electrónica - Departament d'Enginyeria Electrònica
|
Issued date:
|
|
Abstract:
|
[EN] This paper presents an IEEE Std. 1459 power magnitude measurement system working as a part of a power quality improvement structure. It is intended to enhance the performance of selective shunt active power compensators ...[+]
[EN] This paper presents an IEEE Std. 1459 power magnitude measurement system working as a part of a power quality improvement structure. It is intended to enhance the performance of selective shunt active power compensators (SAPCs). The measurements system includes a synchronization structure to estimate the fundamental positive-sequence component of grid voltages in distorted and asymmetric three-phase systems. The synchronization signal is used by a sliding window discrete Fourier transformation (SDFT) recursive algorithm to obtain the fundamental components of the voltages and currents. This algorithm extremely reduces the computational cost compared
with the classic SDFT implementation. This strategy allows for a sample-by-sample quasicontinuous calculation of all power quantities, as well as the nonefficient currents. These magnitudes had been used to generate the reference currents for an SAPC achieving a quasicontinuous compensation of the nonefficient power quantities. Simulation and experimental results demonstrate that the proposed measurements system operates correctly
under all electrical power network conditions.
[-]
|
Subjects:
|
Harmonics
,
IEEE Std. 1459
,
Measurements system
,
Power quality
,
Power systems
,
Unbalanced power
|
Copyrigths:
|
Cerrado |
Source:
|
IEEE Transactions on Instrumentation and Measurement. (issn:
0018-9456
) (eissn:
1557-9662
)
|
DOI:
|
10.1109/TIM.2013.2270901
|
Publisher:
|
Institute of Electrical and Electronics Engineers (IEEE)
|
Publisher version:
|
http://dx.doi.org/10.1109/TIM.2013.2270901
|
Project ID:
|
info:eu-repo/grantAgreement/MICINN//DPI2011-28606/ES/SISTEMAS DE COMPENSACION ACTIVA PARA EL AHORRO ENERGETICO Y LA MEJORA DE LA CALIDAD DEL SUMINISTRO ELECTRICO./
|
Thanks:
|
This work was supported in part by the Ministerio de Economia y Competitividad under Grant DPI2011-28606. The Associate Editor coordinating the review process was Dr. Carlo Muscas.
|
Type:
|
Artículo
|