Mota Babiloni, AdriánNavarro Esbri, JoaquinBarragán Cervera, ÁngelMolés Ribera, FranciscoPeris Pérez, Bernardo2015-12-152015-12-152015-040140-7007https://riunet.upv.es/handle/10251/58840[EN] The EU Regulation No 517/2014 is going to phase-out most of the refrigerants commonly used in refrigeration and air conditioning systems (R134a, R404A and R410A) because of their extended use and their high GWP values. There are very different options to replace them; however, no refrigerant has yet imposed. In this paper we review and analyze the different mixtures proposed by the AHRI as alternative refrigerants to those employed currently. These mixtures are composed by HFC refrigerants: R32, R125, R152a and R134a; and HFO refrigerants: R1234yf and R1234ze(E). It is concluded, from the theoretical analysis, that most of the new HFO/HFC mixtures perform under the HFC analyzed (although some experimental studies show the contrary) and, in most cases, do not meet the GWP restrictions approved by the European normative. Furthermore, some of the mixtures proposed would have problems due to their flammability.Reserva de todos los derechosRefrigerationAir conditioningGWPEU Regulation No 517/2014HFO/HFC mixturesHFC replacementAnalysis based on EU Regulation No 517/2014 of new HFC/HFO mixtures as alternatives of high GWP refrigerants in refrigeration and HVAC systemsAnalyse basee sur le r eglement de l 'UE No 517/2014 de nouveaux melanges HFC/HFO comme alternatives aux frigorigenes a GWP elev e dans des syst emes frigorifiques et de genie climatiqueArtículo10.1016/j.ijrefrig.2014.12.021Abierto