Mostrar el registro sencillo del ítem
dc.contributor.author | Corberán, José M. | es_ES |
dc.contributor.author | Martínez-Ballester, Santiago | es_ES |
dc.contributor.author | Gonzálvez-Maciá, José | es_ES |
dc.contributor.author | La-Barbera, Claudio | es_ES |
dc.date.accessioned | 2022-02-15T19:03:48Z | |
dc.date.available | 2022-02-15T19:03:48Z | |
dc.date.issued | 2016 | es_ES |
dc.identifier.uri | http://hdl.handle.net/10251/180861 | |
dc.description.abstract | [EN] Single phase formulas based on logarithmic mean temperature difference (LMTD) or Effectiveness (E-NTU) are widely and wrongly used for the thermal analysis of evaporators and condensers. Those formulas do not take into account that temperature variation during phase change is due to pressure variation and/or concentration changes when using nonazeotropic refrigerant mixtures. This paper first presents the correct evaluation of the mean temperature difference and effectiveness, for parallel and counter flow arrangements, under the hypothesis of linear temperature variation, for both evaporator and condenser cases. Then, the analytical solution is employed to evaluate the error of applying the single phase formulas of LMTD and Effectiveness to the phase change part of evaporators and condensers | es_ES |
dc.language | Inglés | es_ES |
dc.publisher | IOP Publishing | es_ES |
dc.relation.ispartof | Journal of Physics: Conference Series (Online) | es_ES |
dc.rights | Reconocimiento (by) | es_ES |
dc.subject.classification | MAQUINAS Y MOTORES TERMICOS | es_ES |
dc.title | Error estimation of single phase effectiveness and LMTD methodologies when applied to heat exchangers with phase change | es_ES |
dc.type | Artículo | es_ES |
dc.identifier.doi | 10.1088/1742-6596/745/3/032125 | es_ES |
dc.rights.accessRights | Abierto | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Instituto de Ingeniería Energética - Institut d'Enginyeria Energètica | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Departamento de Termodinámica Aplicada - Departament de Termodinàmica Aplicada | es_ES |
dc.description.bibliographicCitation | Corberán, JM.; Martínez-Ballester, S.; Gonzálvez-Maciá, J.; La-Barbera, C. (2016). Error estimation of single phase effectiveness and LMTD methodologies when applied to heat exchangers with phase change. Journal of Physics: Conference Series (Online). 745(3):1-8. https://doi.org/10.1088/1742-6596/745/3/032125 | es_ES |
dc.description.accrualMethod | S | es_ES |
dc.relation.publisherversion | https://doi.org/10.1088/1742-6596/745/3/032125 | es_ES |
dc.description.upvformatpinicio | 1 | es_ES |
dc.description.upvformatpfin | 8 | es_ES |
dc.type.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.description.volume | 745 | es_ES |
dc.description.issue | 3 | es_ES |
dc.identifier.eissn | 1742-6596 | es_ES |
dc.relation.pasarela | S\357780 | es_ES |