Impact of lubricant in the performance of variable speed heat pumps working with R290

RiuNet: Repositorio Institucional de la Universidad Politécnica de Valencia

Compartir/Enviar a

Citas

Estadísticas

  • Estadisticas de Uso

Impact of lubricant in the performance of variable speed heat pumps working with R290

Mostrar el registro sencillo del ítem

Ficheros en el ítem

dc.contributor.author Ossorio-Santiago, Rubén Josep es_ES
dc.contributor.author Navarro-Peris, Emilio es_ES
dc.contributor.author Barta, Riley B. es_ES
dc.date.accessioned 2024-02-29T19:03:15Z
dc.date.available 2024-02-29T19:03:15Z
dc.date.issued 2022-11 es_ES
dc.identifier.issn 0140-7007 es_ES
dc.identifier.uri http://hdl.handle.net/10251/202858
dc.description.abstract [EN] Modulating the speed of the compressors and adapting its capacity to the required load has led to a decrease in the annual energy consumption in many applications. However, in the compressor, having adequate lubrication at low speeds usually implies discharging too much lubricant at higher speeds. Although necessary for compressor operation, lubricating oil acts as a contaminant in the rest of the system. Consequently, manufac- turers have to consider the oil circulation rate (OCR), as it limits the speed range of the compressor. In a previous study, a compressor was tested over its speed range (30 - 110 Hz), working with R290 and POE68 as a lubricant. Experimental data confirm the increase of OCR with speed and suggests that working with R290-POE68 could imply higher OCR values compared to other refrigerant-oil mixtures. In this study, the impact of the OCR in the performance of a R290 heat pump was theoretically assessed. Three contributions were studied: The heat transfer coefficient (HTC) reduction in the evaporator, the effect of refrigerant being solved in oil and finally, and the impact of oil in the compressor. It was found that OCR values of 5% could decrease the coefficient of performance (COP) by more than 20%. es_ES
dc.description.sponsorship The authors would like to acknowledge the Spanish ' MINISTERIO DE ECONOMIA Y COMPETITIVIDAD' , through the project ref- ENE2017 - 83665-C2 - 1-P 'Maximización de la eficiencia y minimización del impacto ambiental de bombas de calor para la descarbonización de la calefacción/acs en los edificios de consumo casi nulo' for the given support. In addition, Ruben Ossorio would like to thank the Spanish government for his PhD scholarship with reference PRE2018 - 083535. es_ES
dc.language Inglés es_ES
dc.publisher Elsevier es_ES
dc.relation.ispartof International Journal of Refrigeration es_ES
dc.rights Reconocimiento (by) es_ES
dc.subject OCR es_ES
dc.subject Heat transfer coefficient es_ES
dc.subject Solubility es_ES
dc.subject Oil effect es_ES
dc.subject Débit de circulation de l¿huile es_ES
dc.subject Coefficient de transfert de chaleur es_ES
dc.subject Solubilité es_ES
dc.subject Effet de l'huile es_ES
dc.subject Compresseur à spirale es_ES
dc.subject Propane es_ES
dc.subject.classification MAQUINAS Y MOTORES TERMICOS es_ES
dc.title Impact of lubricant in the performance of variable speed heat pumps working with R290 es_ES
dc.title.alternative Impact du lubrifiant sur les performances des pompes à chaleur à vitesse variable fonctionnant au R290 es_ES
dc.type Artículo es_ES
dc.identifier.doi 10.1016/j.ijrefrig.2022.10.003 es_ES
dc.relation.projectID info:eu-repo/grantAgreement/AEI/Plan Estatal de Investigación Científica y Técnica y de Innovación 2013-2016/ENE2017-83665-C2-1-P/ES/MAXIMIZACION DE LA EFICIENCIA Y MINIMIZACION DEL IMPACTO AMBIENTAL DE BOMBAS DE CALOR PARA LA DESCARBONIZACION DE LA CALEFACCION%2FACS EN LOS EDIFICIOS DE CONSUMO CASI NULO/ es_ES
dc.relation.projectID info:eu-repo/grantAgreement/AEI//PRE2018-083535//AYUDA PARA CONTRATO PREDOCTORAL PARA LA FORMACION DE DOCTORES-OSSORIO SANTIAGO, RUBEN. PROYECTO: MAXIMIZACION DE LA EFICIENCIA Y MINIMIZACION DEL IMPACTO AMBIENTAL DE BOMBAS DE CALOR PARA LA DESCARBONIZACION DE LA CALEFACCION/ es_ES
dc.rights.accessRights Abierto es_ES
dc.contributor.affiliation Universitat Politècnica de València. Escuela Técnica Superior de Ingenieros Industriales - Escola Tècnica Superior d'Enginyers Industrials es_ES
dc.description.bibliographicCitation Ossorio-Santiago, RJ.; Navarro-Peris, E.; Barta, RB. (2022). Impact of lubricant in the performance of variable speed heat pumps working with R290. International Journal of Refrigeration. 145:436-445. https://doi.org/10.1016/j.ijrefrig.2022.10.003 es_ES
dc.description.accrualMethod S es_ES
dc.relation.publisherversion https://doi.org/10.1016/j.ijrefrig.2022.10.003 es_ES
dc.description.upvformatpinicio 436 es_ES
dc.description.upvformatpfin 445 es_ES
dc.type.version info:eu-repo/semantics/publishedVersion es_ES
dc.description.volume 145 es_ES
dc.relation.pasarela S\481538 es_ES
dc.contributor.funder Agencia Estatal de Investigación es_ES
dc.contributor.funder Universitat Politècnica de València es_ES


Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem