An Indirect Procedure for Real-Time Monitoring the Neutral Conductor Deterioration in Three-Phase Distribution Networks

RiuNet: Repositorio Institucional de la Universidad Politécnica de Valencia

Compartir/Enviar a

Citas

Estadísticas

  • Estadisticas de Uso

An Indirect Procedure for Real-Time Monitoring the Neutral Conductor Deterioration in Three-Phase Distribution Networks

Mostrar el registro sencillo del ítem

Ficheros en el ítem

dc.contributor.author León-Martínez, Vicente es_ES
dc.contributor.author Montañana-Romeu, Joaquín es_ES
dc.contributor.author Peñalvo-López, Elisa es_ES
dc.contributor.author Leon-Vinet, Amparo es_ES
dc.contributor.author Cano-Martínez, Jorge es_ES
dc.date.accessioned 2024-07-01T18:37:52Z
dc.date.available 2024-07-01T18:37:52Z
dc.date.issued 2023-04 es_ES
dc.identifier.uri http://hdl.handle.net/10251/205668
dc.description.abstract [EN] An indirect procedure for real-time monitoring the neutral conductor condition in threephase distribution networks, based on watching over the growth of a novel parameter (Dt), has been described in this paper. The parameter Dt has been defined as the relationship between the neutral-displacement power and Buchholz¿s apparent power measured at the fundamental frequency in the loads of the distribution networks for any condition of the neutral conductor and in its nominal conditions. The effectiveness of this procedure has been compared with other traditional indirect procedures, such as the surveillance of the RMS values of the line-to-neutral load voltages or their zero-sequence component. The practical application on a real distribution network reveals that the growth of the parameter Dt in the early stages of the breaking process of the neutral conductor follows a straight line whose equation is known for each length and section of that conductor, regardless of the loads and the voltage regulation of the transformer of the distribution network. This characteristic of the Dt parameter shows that the proposed procedure is suitable for monitoring neutral conductor deterioration and can be used for preventive maintenance of distribution networks. es_ES
dc.description.sponsorship This research was funded by the European Commission under the LIFE Program, project LIFE21-CET-LOCAL-GENERA, grant number 101077073. es_ES
dc.language Inglés es_ES
dc.publisher MDPI AG es_ES
dc.relation.ispartof Machines (Basel) es_ES
dc.rights Reconocimiento (by) es_ES
dc.subject Neutral conductor state es_ES
dc.subject Neutral conductor breakage es_ES
dc.subject Monitoring es_ES
dc.subject Distribution networks es_ES
dc.subject Apparent power es_ES
dc.subject Neutral-displacement power es_ES
dc.subject.classification INGENIERIA ELECTRICA es_ES
dc.title An Indirect Procedure for Real-Time Monitoring the Neutral Conductor Deterioration in Three-Phase Distribution Networks es_ES
dc.type Artículo es_ES
dc.identifier.doi 10.3390/machines11040444 es_ES
dc.relation.projectID info:eu-repo/grantAgreement/COMISION DE LAS COMUNIDADES EUROPEA//LIFE21-CET-LOCAL//Re-vitalising Energy Transition in Touristic Islands/ es_ES
dc.rights.accessRights Abierto es_ES
dc.description.bibliographicCitation León-Martínez, V.; Montañana-Romeu, J.; Peñalvo-López, E.; Leon-Vinet, A.; Cano-Martínez, J. (2023). An Indirect Procedure for Real-Time Monitoring the Neutral Conductor Deterioration in Three-Phase Distribution Networks. Machines (Basel). 11(4). https://doi.org/10.3390/machines11040444 es_ES
dc.description.accrualMethod S es_ES
dc.relation.publisherversion https://doi.org/10.3390/machines11040444 es_ES
dc.type.version info:eu-repo/semantics/publishedVersion es_ES
dc.description.volume 11 es_ES
dc.description.issue 4 es_ES
dc.identifier.eissn 2075-1702 es_ES
dc.relation.pasarela S\486752 es_ES
dc.contributor.funder COMISION DE LAS COMUNIDADES EUROPEA es_ES
upv.costeAPC 1500 es_ES


Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem