Energy influence of the IHX with R22 drop-in and long-term substitutes in refrigeration plants

RiuNet: Repositorio Institucional de la Universidad Politécnica de Valencia

Compartir/Enviar a

Citas

Estadísticas

  • Estadisticas de Uso

Energy influence of the IHX with R22 drop-in and long-term substitutes in refrigeration plants

Mostrar el registro sencillo del ítem

Ficheros en el ítem

dc.contributor.author Cabello, R. es_ES
dc.contributor.author Torrella Alcaraz, Enrique es_ES
dc.contributor.author Llopis, R. es_ES
dc.contributor.author Sanchez, D. es_ES
dc.contributor.author Larumbe, J.A. es_ES
dc.date.accessioned 2015-06-29T07:22:43Z
dc.date.available 2015-06-29T07:22:43Z
dc.date.issued 2013-01-10
dc.identifier.issn 1359-4311
dc.identifier.uri http://hdl.handle.net/10251/52401
dc.description.abstract This work focuses on the investigation of new drop-in or long-term refrigerants for low evaporating temperatures that can be used as substitutes for HCFC-22, which is gradually being phased-out. This process is already in progress in European countries (Regulation CE-1005/2009) and has been accelerated in Article 5 Countries of the Montreal Protocol. Specifically, in this work the energy influence of the suction line/liquid line heat exchanger on the new substitute fluids is addressed from an experimental approach. The study has been based on experimental measurements in a single-stage vapour compression refrigeration plant, which has been tested in the same external conditions operating with and without an Internal Heat Exchanger (IHX). The energy influence of the IHX working with R22 and three potential substitutes for low temperature applications, the chlorine-free drop-in fluids R417B and R422A and the chlorine-free long-term substitute R404A has been analysed. From the experimental results, reductions in capacity and COP have been observed when R22 is replaced by the drop-in fluids, although the presence of an IHX can help to lessen these reductions. Furthermore, the criteria that are usually employed to determine the energy advantage or disadvantage of the use of the IHX with the new refrigerants have been tested, the results confirming that they remain valid for them. es_ES
dc.language Inglés es_ES
dc.publisher Elsevier es_ES
dc.relation.ispartof Applied Thermal Engineering es_ES
dc.rights Reserva de todos los derechos es_ES
dc.subject HCFC replacements es_ES
dc.subject Drop-in refrigerants es_ES
dc.subject Internal Heat Exchanger es_ES
dc.subject Energy efficiency es_ES
dc.subject R22 es_ES
dc.subject.classification MAQUINAS Y MOTORES TERMICOS es_ES
dc.title Energy influence of the IHX with R22 drop-in and long-term substitutes in refrigeration plants es_ES
dc.type Artículo es_ES
dc.identifier.doi 10.1016/j.applthermaleng.2012.06.008
dc.rights.accessRights Cerrado es_ES
dc.contributor.affiliation Universitat Politècnica de València. Departamento de Termodinámica Aplicada - Departament de Termodinàmica Aplicada es_ES
dc.description.bibliographicCitation Cabello, R.; Torrella Alcaraz, E.; Llopis, R.; Sanchez, D.; Larumbe, J. (2013). Energy influence of the IHX with R22 drop-in and long-term substitutes in refrigeration plants. Applied Thermal Engineering. 50(1):260-267. doi:10.1016/j.applthermaleng.2012.06.008 es_ES
dc.description.accrualMethod S es_ES
dc.relation.publisherversion http://dx.doi.org/10.1016/j.applthermaleng.2012.06.008 es_ES
dc.description.upvformatpinicio 260 es_ES
dc.description.upvformatpfin 267 es_ES
dc.type.version info:eu-repo/semantics/publishedVersion es_ES
dc.description.volume 50 es_ES
dc.description.issue 1 es_ES
dc.relation.senia 237705
dc.identifier.eissn 1873-5606


Este ítem aparece en la(s) siguiente(s) colección(ones)