dc.description.abstract | [EN] This work presents an experimental analysis of a non-flammable R1234ze(E)/R134a mixture (R450A) as R134a drop-in replacement. While R134a has a high GWP value (1430), the R450A GWP is only 547. The experimental tests are carried out in a vapour compression plant equipped with a variable-speed compressor. The replacement suitability has been studied combining different operating conditions: evaporation temperature, condensation temperature and the use of an internal heat exchanger (IHX). The drop-in cooling capacity of R450A compared with R134a is 6% lower as average. R450A COP is even higher to those resulting with R134a (approximately 1%). The discharge temperature of R450A is lower than that of R134a, 2K as average. The IHX has a similar positive influence on the energy performance of both fluids. In conclusion, R450A can be considered as a good candidate to replace R134a. | es_ES |
dc.description.sponsorship | The authors thankfully acknowledge "Ministerio de Educacion, Cultura y Deporte" for supporting this work through "Becas y Contratos de Formacion de Profesorado Universitario del Programa Nacional de Formacion de Recursos Humanos de Investigacion del ejercicio 2012". | |
dc.language | Inglés | es_ES |
dc.publisher | Elsevier | es_ES |
dc.relation.ispartof | International Journal of Refrigeration | es_ES |
dc.rights | Reserva de todos los derechos | es_ES |
dc.subject | Refrigeration | es_ES |
dc.subject | R450A | es_ES |
dc.subject | R134a | es_ES |
dc.subject | Mixture | es_ES |
dc.subject | Energy efficiency | es_ES |
dc.subject | Drop-in | es_ES |
dc.title | Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement | es_ES |
dc.type | Artículo | es_ES |
dc.identifier.doi | 10.1016/j.ijrefrig.2014.12.010 | |
dc.rights.accessRights | Abierto | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Departamento de Termodinámica Aplicada - Departament de Termodinàmica Aplicada | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Instituto de Seguridad Industrial, Radiofísica y Medioambiental - Institut de Seguretat Industrial, Radiofísica i Mediambiental | es_ES |
dc.description.bibliographicCitation | Mota Babiloni, A.; Navarro Esbri, J.; Barragán Cervera, Á.; Moles Ribera, F.; Peris Pérez, B. (2015). Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement. International Journal of Refrigeration. 51:52-58. doi:10.1016/j.ijrefrig.2014.12.010 | es_ES |
dc.description.accrualMethod | S | es_ES |
dc.relation.publisherversion | http://dx.doi.org/10.1016/j.ijrefrig.2014.12.010 | es_ES |
dc.description.upvformatpinicio | 52 | es_ES |
dc.description.upvformatpfin | 58 | es_ES |
dc.type.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.description.volume | 51 | es_ES |
dc.relation.senia | 279955 | es_ES |