Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement

RiuNet: Repositorio Institucional de la Universidad Politécnica de Valencia

Compartir/Enviar a

Citas

Estadísticas

  • Estadisticas de Uso

Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement

Mostrar el registro sencillo del ítem

Ficheros en el ítem

dc.contributor.author Mota Babiloni, Adrián es_ES
dc.contributor.author Navarro Esbri, Joaquin es_ES
dc.contributor.author Barragán Cervera, Ángel es_ES
dc.contributor.author Moles Ribera, Francisco es_ES
dc.contributor.author Peris Pérez, Bernardo es_ES
dc.date.accessioned 2015-12-15T08:29:11Z
dc.date.available 2015-12-15T08:29:11Z
dc.date.issued 2015-03
dc.identifier.issn 0140-7007
dc.identifier.uri http://hdl.handle.net/10251/58807
dc.description.abstract [EN] This work presents an experimental analysis of a non-flammable R1234ze(E)/R134a mixture (R450A) as R134a drop-in replacement. While R134a has a high GWP value (1430), the R450A GWP is only 547. The experimental tests are carried out in a vapour compression plant equipped with a variable-speed compressor. The replacement suitability has been studied combining different operating conditions: evaporation temperature, condensation temperature and the use of an internal heat exchanger (IHX). The drop-in cooling capacity of R450A compared with R134a is 6% lower as average. R450A COP is even higher to those resulting with R134a (approximately 1%). The discharge temperature of R450A is lower than that of R134a, 2K as average. The IHX has a similar positive influence on the energy performance of both fluids. In conclusion, R450A can be considered as a good candidate to replace R134a. es_ES
dc.description.sponsorship The authors thankfully acknowledge "Ministerio de Educacion, Cultura y Deporte" for supporting this work through "Becas y Contratos de Formacion de Profesorado Universitario del Programa Nacional de Formacion de Recursos Humanos de Investigacion del ejercicio 2012".
dc.language Inglés es_ES
dc.publisher Elsevier es_ES
dc.relation.ispartof International Journal of Refrigeration es_ES
dc.rights Reserva de todos los derechos es_ES
dc.subject Refrigeration es_ES
dc.subject R450A es_ES
dc.subject R134a es_ES
dc.subject Mixture es_ES
dc.subject Energy efficiency es_ES
dc.subject Drop-in es_ES
dc.title Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement es_ES
dc.type Artículo es_ES
dc.identifier.doi 10.1016/j.ijrefrig.2014.12.010
dc.rights.accessRights Abierto es_ES
dc.contributor.affiliation Universitat Politècnica de València. Departamento de Termodinámica Aplicada - Departament de Termodinàmica Aplicada es_ES
dc.contributor.affiliation Universitat Politècnica de València. Instituto de Seguridad Industrial, Radiofísica y Medioambiental - Institut de Seguretat Industrial, Radiofísica i Mediambiental es_ES
dc.description.bibliographicCitation Mota Babiloni, A.; Navarro Esbri, J.; Barragán Cervera, Á.; Moles Ribera, F.; Peris Pérez, B. (2015). Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement. International Journal of Refrigeration. 51:52-58. doi:10.1016/j.ijrefrig.2014.12.010 es_ES
dc.description.accrualMethod S es_ES
dc.relation.publisherversion http://dx.doi.org/10.1016/j.ijrefrig.2014.12.010 es_ES
dc.description.upvformatpinicio 52 es_ES
dc.description.upvformatpfin 58 es_ES
dc.type.version info:eu-repo/semantics/publishedVersion es_ES
dc.description.volume 51 es_ES
dc.relation.senia 279955 es_ES