Theoretical energy performance evaluation of different single stage vapour compression refrigeration configurations using R1234yf and R1234ze(E) as working fluids

RiuNet: Repositorio Institucional de la Universidad Politécnica de Valencia

Compartir/Enviar a

Citas

Estadísticas

  • Estadisticas de Uso

Theoretical energy performance evaluation of different single stage vapour compression refrigeration configurations using R1234yf and R1234ze(E) as working fluids

Mostrar el registro sencillo del ítem

Ficheros en el ítem

dc.contributor.author Molés Ribera, Francisco es_ES
dc.contributor.author Navarro Esbri, Joaquin es_ES
dc.contributor.author Peris Pérez, Bernardo es_ES
dc.contributor.author Mota Babiloni, Adrián es_ES
dc.contributor.author Barragán Cervera, Ángel es_ES
dc.date.accessioned 2015-12-15T12:41:32Z
dc.date.available 2015-12-15T12:41:32Z
dc.date.issued 2014-08
dc.identifier.issn 0140-7007
dc.identifier.uri http://hdl.handle.net/10251/58841
dc.description.abstract R1234yf and R1234ze(E) have been proposed as alternatives for R134a in order to work with low GWP refrigerants, but this replacement results generally in a decrease of the performance. For this reason, it is interesting to explore ways to improve the system performance using these refrigerants. In this paper, a comparative study in terms of energy performance of different single stage vapour compression configurations using R1234yf and R1234ze(E) as working fluids has been carried out. The most efficient configuration is the one which uses an expander or an ejector as expansion device. On the other hand, using an internal heat exchanger in a cycle which replaces the expansion valve by an expander or an ejector could produce a detrimental effect on the COP. However, for all the configurations the introduction of an internal heat exchanger produces a significant increment on the cooling capacity. es_ES
dc.language Inglés es_ES
dc.publisher Elsevier es_ES
dc.relation.ispartof International Journal of Refrigeration es_ES
dc.rights Reserva de todos los derechos es_ES
dc.subject Single stage es_ES
dc.subject Refrigeration es_ES
dc.subject R1234yf es_ES
dc.subject R1234ze(E) es_ES
dc.subject Energy efficiency es_ES
dc.title Theoretical energy performance evaluation of different single stage vapour compression refrigeration configurations using R1234yf and R1234ze(E) as working fluids es_ES
dc.title.alternative Evaluation the´orique de la performance e´nerge´tique de diffe´ rentes configurations monoe´tage´es a` compression de vapeur utilisant R1234yf et R1234zeV comme fluides actifs es_ES
dc.type Artículo es_ES
dc.identifier.doi 10.1016/j.ijrefrig.2014.04.025
dc.rights.accessRights Abierto es_ES
dc.contributor.affiliation Universitat Politècnica de València. Departamento de Termodinámica Aplicada - Departament de Termodinàmica Aplicada es_ES
dc.contributor.affiliation Universitat Politècnica de València. Instituto de Seguridad Industrial, Radiofísica y Medioambiental - Institut de Seguretat Industrial, Radiofísica i Mediambiental es_ES
dc.description.bibliographicCitation Molés Ribera, F.; Navarro Esbri, J.; Peris Pérez, B.; Mota Babiloni, A.; Barragán Cervera, Á. (2014). Theoretical energy performance evaluation of different single stage vapour compression refrigeration configurations using R1234yf and R1234ze(E) as working fluids. International Journal of Refrigeration. 44:141-150. doi:10.1016/j.ijrefrig.2014.04.025 es_ES
dc.description.accrualMethod S es_ES
dc.relation.publisherversion http://dx.doi.org/10.1016/j.ijrefrig.2014.04.025 es_ES
dc.description.upvformatpinicio 141 es_ES
dc.description.upvformatpfin 150 es_ES
dc.type.version info:eu-repo/semantics/publishedVersion es_ES
dc.description.volume 44 es_ES
dc.relation.senia 268166 es_ES


Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem