Mostrar el registro sencillo del ítem
dc.contributor.author | Llopis Doménech, Rodrigo | es_ES |
dc.contributor.author | SANZ Kock, Carlos | es_ES |
dc.contributor.author | Cabello, Ramon | es_ES |
dc.contributor.author | Sanchez, Daniel | es_ES |
dc.contributor.author | Torrella Alcaraz, Enrique | es_ES |
dc.date.accessioned | 2016-10-07T12:37:29Z | |
dc.date.available | 2016-10-07T12:37:29Z | |
dc.date.issued | 2015-04-05 | |
dc.identifier.issn | 1359-4311 | |
dc.identifier.uri | http://hdl.handle.net/10251/71401 | |
dc.description.abstract | We present the experimental evaluation of an internal heat exchanger or suction-line/liquid-line heat exchanger in a CO2 subcritical refrigeration plant with gas-cooler. The plant, driven by a 1.5 kW CO2 semi hermetic compressor, uses brazed plate heat exchangers as condenser, evaporator and internal heat exchanger, an air finned tube gas-cooler and an electronic expansion valves. The evaluation (77 steadystates) covers evaporating temperatures from 40 to 25 C and condensing temperatures from 15 to 0 C, always at the nominal speed of the compressor. Here, the effect of the internal heat exchanger on the main energy parameters is analysed, i.e., cooling capacity, COP and heat rejection at gas-cooler and condenser. Also, the effect of the internal heat exchanger in a cascade cycle is analysed theoretically. It has been concluded that the internal heat exchanger does not improve the performance of the subcritical cycle, but it could improve the energy performance if it is used inside a cascade refrigeration system. | es_ES |
dc.description.sponsorship | The authors gratefully acknowledge Jaume I University of Spain, who financed the present study through the research project P1.B2013-10. | en_EN |
dc.language | Inglés | es_ES |
dc.publisher | Elsevier | es_ES |
dc.relation.ispartof | Applied Thermal Engineering | es_ES |
dc.rights | Reconocimiento - No comercial - Sin obra derivada (by-nc-nd) | es_ES |
dc.subject | CO2 | es_ES |
dc.subject | Subcritical | es_ES |
dc.subject | Internal heat exchanger | es_ES |
dc.subject | Cascade | es_ES |
dc.subject | Experimental | es_ES |
dc.subject.classification | MAQUINAS Y MOTORES TERMICOS | es_ES |
dc.title | Experimental evaluation of an internal heat exchanger in a CO2 subcritical refrigeration cycle with gas-cooler | es_ES |
dc.type | Artículo | es_ES |
dc.identifier.doi | 10.1016/j.applthermaleng.2015.01.040 | |
dc.relation.projectID | info:eu-repo/grantAgreement/UJI//P1·B2013-10/ | es_ES |
dc.rights.accessRights | Abierto | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Departamento de Termodinámica Aplicada - Departament de Termodinàmica Aplicada | es_ES |
dc.description.bibliographicCitation | Llopis Doménech, R.; Sanz Kock, C.; Cabello, R.; Sanchez, D.; Torrella Alcaraz, E. (2015). Experimental evaluation of an internal heat exchanger in a CO2 subcritical refrigeration cycle with gas-cooler. Applied Thermal Engineering. 80:31-41. https://doi.org/10.1016/j.applthermaleng.2015.01.040 | es_ES |
dc.description.accrualMethod | S | es_ES |
dc.relation.publisherversion | http://dx.doi.org/10.1016/j.applthermaleng.2015.01.040 | es_ES |
dc.description.upvformatpinicio | 31 | es_ES |
dc.description.upvformatpfin | 41 | es_ES |
dc.type.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.description.volume | 80 | es_ES |
dc.relation.senia | 305857 | es_ES |
dc.contributor.funder | Universitat Jaume I | es_ES |