Mostrar el registro sencillo del ítem
dc.contributor.author | Navarro-Peris, Emilio | es_ES |
dc.contributor.author | Corberán Salvador, José Miguel | es_ES |
dc.contributor.author | Martínez Galván, Israel Octavio | es_ES |
dc.contributor.author | Gonzálvez Maciá, José | es_ES |
dc.date.accessioned | 2017-05-04T13:37:45Z | |
dc.date.available | 2017-05-04T13:37:45Z | |
dc.date.issued | 2012-03 | |
dc.identifier.issn | 0140-7007 | |
dc.identifier.uri | http://hdl.handle.net/10251/80589 | |
dc.description.abstract | The oil temperature in the compressor sump is an important parameter describing the performance of a refrigeration compressor. Its estimation is necessary for evaluation of the lubricant-refrigerant mixture composition and its properties. In contrast, this temperature is not normally measured in compressor performance tests and is unlikely reported by the manufacturers or in the technical literature. In this paper, a set of tests measuring the oil sump temperature for hermetic reciprocating and scroll compressors in a wide range of working conditions is presented. From these results and after a theoretical analysis of the factors having influence on this parameter, a correlation for the oil temperature as a function of compressor inlet and outlet conditions is presented. This correlation allows to estimate the oil sump temperature for scroll and hermetic reciprocating compressors as a function of operation conditions with an error lower than 4 K degree for most of the cases. | es_ES |
dc.description.sponsorship | This work has been partially funded by the Spanish Ministerio de Ciencia e Innovacion through project, ref. DPI 2008-06707-C02-01 (Estudio de optimizacion de equipos frigorificos de aire acondicionado para su funcionamiento con refrigerantes naturales (hidrocarburos)). | en_EN |
dc.language | Inglés | es_ES |
dc.publisher | Elsevier | es_ES |
dc.relation.ispartof | International Journal of Refrigeration | es_ES |
dc.rights | Reserva de todos los derechos | es_ES |
dc.subject | Lubricant | es_ES |
dc.subject | Oil | es_ES |
dc.subject | Performance | es_ES |
dc.subject | Reciprocating compressor | es_ES |
dc.subject | Refrigerants | es_ES |
dc.subject | Temperature | es_ES |
dc.subject.classification | MAQUINAS Y MOTORES TERMICOS | es_ES |
dc.subject.classification | FISICA APLICADA | es_ES |
dc.title | Oil sump temperature in hermetic compressors for heat pump applications | es_ES |
dc.type | Artículo | es_ES |
dc.identifier.doi | 10.1016/j.ijrefrig.2011.10.006 | |
dc.relation.projectID | info:eu-repo/grantAgreement/MICINN//DPI2008-06707-C02-01/ES/ESTUDIO DE OPTIMIZACION DE EQUIPOS FRIGORIFICOS Y DE AIRE ACONDICIONADO PARA SU FUNCIONAMIENTO CON REFRIGERANTES NATURALES HIDROCARBUROS/ | es_ES |
dc.rights.accessRights | Abierto | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Escuela Técnica Superior de Ingenieros Industriales - Escola Tècnica Superior d'Enginyers Industrials | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Instituto de Ingeniería Energética - Institut d'Enginyeria Energètica | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Escuela Técnica Superior de Ingeniería del Diseño - Escola Tècnica Superior d'Enginyeria del Disseny | es_ES |
dc.description.bibliographicCitation | Navarro-Peris, E.; Corberán Salvador, JM.; Martínez Galván, IO.; Gonzálvez Maciá, J. (2012). Oil sump temperature in hermetic compressors for heat pump applications. International Journal of Refrigeration. 35(2):397-406. https://doi.org/10.1016/j.ijrefrig.2011.10.006 | es_ES |
dc.description.accrualMethod | S | es_ES |
dc.relation.publisherversion | http://dx.doi.org/10.1016/j.ijrefrig.2011.10.006 | es_ES |
dc.description.upvformatpinicio | 397 | es_ES |
dc.description.upvformatpfin | 406 | es_ES |
dc.type.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.description.volume | 35 | es_ES |
dc.description.issue | 2 | es_ES |
dc.relation.senia | 211772 | es_ES |
dc.contributor.funder | Ministerio de Ciencia e Innovación | es_ES |