Mostrar el registro sencillo del ítem
dc.contributor.author | Cervera Vázquez, Javier | es_ES |
dc.contributor.author | Montagud Montalvá, Carla Isabel | es_ES |
dc.contributor.author | Corberán Salvador, José Miguel | es_ES |
dc.date.accessioned | 2017-05-26T07:29:06Z | |
dc.date.available | 2017-05-26T07:29:06Z | |
dc.date.issued | 2016 | |
dc.identifier.issn | 2374-4731 | |
dc.identifier.uri | http://hdl.handle.net/10251/81804 | |
dc.description.abstract | [♪EN] This paper presents a sizing study of the buffer tank in chilled water A/C systems. In order to find out the adequate sizing criteria for buffer tanks in these kind of installations, a review of different manufacturers' guidelines was carried out and it was concluded that there are three main operation parameters affected by the volume of the tank: the ON cycle time, the OFF cycle time, and the number of starts per hour of the chiller compressor. In order to better understand the influence of each parameter, a theoretical analysis was carried out where the impact of the building thermal load in different design criteria was also studied. After a thorough analysis of all the studied criteria, it was concluded that the minimum ON cycle time which is necessary to ensure that the oil returns to the compressor is the most critical criterion. Finally, a design guideline is proposed by the authors in order to determine the minimum volume of the buffer tank, mainly depending on the capacity of the chiller and the temperature deadband of the thermostat control. | es_ES |
dc.description.sponsorship | This work was supported by the "Programa de Ayudas de Investigacion y Desarrollo (PAID)" of the Universitat Politecnica de Valencia. This work was also supported under the FP7 programme "Advanced ground source heat pump systems for heating and cooling in Mediterranean climate" (GROUND-MED project). | en_EN |
dc.language | Inglés | es_ES |
dc.publisher | Taylor & Francis | es_ES |
dc.relation.ispartof | Science and Technology for the Built Environment | es_ES |
dc.rights | Reserva de todos los derechos | es_ES |
dc.subject | Buffer tank | es_ES |
dc.subject | Chiller operation | es_ES |
dc.subject | Hydraulic design | es_ES |
dc.subject.classification | MAQUINAS Y MOTORES TERMICOS | es_ES |
dc.title | Sizing of the buffer tank in chilled water distribution air-conditioning systems | es_ES |
dc.type | Artículo | es_ES |
dc.identifier.doi | 10.1080/23744731.2016.1131569 | |
dc.relation.projectID | info:eu-repo/grantAgreement/EC/FP7/218895/EU/Advanced ground source heat pump systems for heating and cooling in Mediterranean climate/ | es_ES |
dc.rights.accessRights | Abierto | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Escuela Técnica Superior de Ingenieros Industriales - Escola Tècnica Superior d'Enginyers Industrials | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Instituto de Ingeniería Energética - Institut d'Enginyeria Energètica | es_ES |
dc.description.bibliographicCitation | Cervera Vázquez, J.; Montagud Montalvá, CI.; Corberán Salvador, JM. (2016). Sizing of the buffer tank in chilled water distribution air-conditioning systems. Science and Technology for the Built Environment. 22(3):290-298. https://doi.org/10.1080/23744731.2016.1131569 | es_ES |
dc.description.accrualMethod | S | es_ES |
dc.relation.publisherversion | http://doi.org/10.1080/23744731.2016.1131569 | es_ES |
dc.description.upvformatpinicio | 290 | es_ES |
dc.description.upvformatpfin | 298 | es_ES |
dc.type.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.description.volume | 22 | es_ES |
dc.description.issue | 3 | es_ES |
dc.relation.senia | 303431 | es_ES |
dc.identifier.eissn | 2374-474X | |
dc.contributor.funder | European Commission | |
dc.contributor.funder | Universitat Politècnica de València |