Mostrar el registro sencillo del ítem
dc.contributor.author | Navarro-Esbrí, J. | es_ES |
dc.contributor.author | Milián Sánchez, Víctor | es_ES |
dc.contributor.author | Mota Babiloni, Adrián | es_ES |
dc.contributor.author | Molés Ribera, Francisco | es_ES |
dc.contributor.author | Verdú Martín, Gumersindo Jesús | es_ES |
dc.date.accessioned | 2017-07-03T07:35:36Z | |
dc.date.available | 2017-07-03T07:35:36Z | |
dc.date.issued | 2015-10-03 | |
dc.identifier.issn | 2374-4731 | |
dc.identifier.uri | http://hdl.handle.net/10251/84291 | |
dc.description.abstract | In this paper, the influence of different mean void fraction correlations on a shell-and-tube evaporator dynamic model performance has been evaluated. The model proposed is based on the moving boundary approach and includes the expansion valve modelling. Several transient tests, using R134a as working fluid, have been carried out varying refrigerant mass flow, inlet enthalpy and secondary fluid flow. Then, the model performance, using different mean void fractions, is analysed from the system model outputs (evaporating pressure, refrigerant outlet temperature and condensing water outlet temperature). The slip ratio expressions selected are: homogenous, momentum flux model, Zivi's, Chisholm's and Smith's correlations. The results of the comparison between experimental and model predictions depend on the transient characteristics and there is not a single slip ratio correlation that provides the best performance in all the cases analysed. | es_ES |
dc.language | Inglés | es_ES |
dc.publisher | Taylor & Francis | es_ES |
dc.relation.ispartof | Science and Technology for the Built Environment | es_ES |
dc.rights | Reserva de todos los derechos | es_ES |
dc.subject | Evaporator | es_ES |
dc.subject | Dynamic model | es_ES |
dc.subject | Mean void fraction | es_ES |
dc.subject | Slip ratio | es_ES |
dc.subject | Refrigeration | es_ES |
dc.subject.classification | INGENIERIA NUCLEAR | es_ES |
dc.title | Effect of mean void fraction correlations on a shell-and-tube evaporator dynamic model performance | es_ES |
dc.type | Artículo | es_ES |
dc.identifier.doi | 10.1080/23744731.2015.1034594 | |
dc.rights.accessRights | Abierto | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Departamento de Ingeniería Química y Nuclear - Departament d'Enginyeria Química i Nuclear | es_ES |
dc.contributor.affiliation | Universitat Politècnica de València. Instituto de Seguridad Industrial, Radiofísica y Medioambiental - Institut de Seguretat Industrial, Radiofísica i Mediambiental | es_ES |
dc.description.bibliographicCitation | Navarro-Esbrí, J.; Milián Sánchez, V.; Mota Babiloni, A.; Molés Ribera, F.; Verdú Martín, GJ. (2015). Effect of mean void fraction correlations on a shell-and-tube evaporator dynamic model performance. Science and Technology for the Built Environment. 21(7):1057-1072. doi:10.1080/23744731.2015.1034594 | es_ES |
dc.description.accrualMethod | S | es_ES |
dc.relation.publisherversion | http://doi.org/10.1080/23744731.2015.1034594 | es_ES |
dc.description.upvformatpinicio | 1057 | es_ES |
dc.description.upvformatpfin | 1072 | es_ES |
dc.type.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.description.volume | 21 | es_ES |
dc.description.issue | 7 | es_ES |
dc.relation.senia | 290730 | es_ES |
dc.identifier.eissn | 2374-474X |