Experimental evaluation of an internal heat exchanger in a CO2 subcritical refrigeration cycle with gas-cooler

Handle

https://riunet.upv.es/handle/10251/71401

Cita bibliográfica

Llopis Doménech, R.; Sanz Kock, C.; Cabello, R.; Sanchez, D.; Torrella Alcaraz, E. (2015). Experimental evaluation of an internal heat exchanger in a CO2 subcritical refrigeration cycle with gas-cooler. Applied Thermal Engineering. 80:31-41. https://doi.org/10.1016/j.applthermaleng.2015.01.040

Titulación

Resumen

We present the experimental evaluation of an internal heat exchanger or suction-line/liquid-line heat exchanger in a CO2 subcritical refrigeration plant with gas-cooler. The plant, driven by a 1.5 kW CO2 semi hermetic compressor, uses brazed plate heat exchangers as condenser, evaporator and internal heat exchanger, an air finned tube gas-cooler and an electronic expansion valves. The evaluation (77 steadystates) covers evaporating temperatures from 40 to 25 C and condensing temperatures from 15 to 0 C, always at the nominal speed of the compressor. Here, the effect of the internal heat exchanger on the main energy parameters is analysed, i.e., cooling capacity, COP and heat rejection at gas-cooler and condenser. Also, the effect of the internal heat exchanger in a cascade cycle is analysed theoretically. It has been concluded that the internal heat exchanger does not improve the performance of the subcritical cycle, but it could improve the energy performance if it is used inside a cascade refrigeration system.

Fuente

Applied Thermal Engineering issn: 1359-4311

Enlaces relacionados

URL