Thermal comparison of two borehole heat exchangers

dc.contributor.advisorPalm, Björn Einares_ES
dc.contributor.authorTen Palomares, Mariaes_ES
dc.date.accessioned2013-12-16T13:14:25Z
dc.date.available2013-12-16T13:14:25Z
dc.date.created2008-06
dc.date.issued2013-12-16
dc.description.abstractConsulta en la Biblioteca ETSI Industriales (7779)es_ES
dc.description.abstract[EN] Vertical borehole heat exchangers are one of the most commonly used collectors for ground source heat pumps. This Master¿s Thesis presents an extensive comparison between two different borehole heat exchangers of a ground source installation located in the south of Stockholm, Sweden. A typical U-pipe heat exchanger is compared to a U-pipe heat exchanger equipped with spacers between pipes. The comparison is based on temperature measurements using thermocouples and optical fibre cables. The undisturbed ground temperature was measured before the system started up. Besides, two different periods of measurements were carried out. The first measurements studied the secondary working fluid temperature profiles during 18 days. In the second measurements the temperature profiles of three different flow regimes were analyzed. The ground water flow outside the boreholes was also studied in both measurement periods. Results from the undisturbed ground show that the geothermal gradient appears at half of the borehole length. From the first measurements results it was not possible to determine which collector is better due to uncertainties in the measurement conditions. The second measurement period shows that the extracted heat increases as the flow becomes more turbulent. The typical U-pipe borehole heat exchanger was demonstrated to extract a major amount of heat from the ground although the differences between collectors are not substantially significant.en_EN
dc.description.accrualMethodArchivo delegadoes_ES
dc.description.bibliographicCitationTen Palomares, M. (2008). Thermal comparison of two borehole heat exchangers. https://riunet.upv.es/handle/10251/34539.es_ES
dc.identifier.urihttps://riunet.upv.es/handle/10251/34539
dc.languageIngléses_ES
dc.publisherUniversitat Politècnica de Valènciaes_ES
dc.rightsReserva de todos los derechoses_ES
dc.rights.accessRightsCerradoes_ES
dc.subjectConsulta en la Biblioteca ETSI Industrialeses_ES
dc.subjectIntercambiadores de calores_ES
dc.subject.classificationTECNOLOGIA ELECTRONICAes_ES
dc.subject.otherIngeniero Industrial-Enginyer Industriales_ES
dc.titleThermal comparison of two borehole heat exchangerses_ES
dc.typeProyecto/Trabajo fin de carrera/gradoes_ES
dspace.entity.typePublication
upv.uuideeaffe9e-def5-4654-a4ed-2ab2da4bef18es_ES

Archivos

Bloque original

Mostrando 1 - 1 de 1
Cargando...
Miniatura
Nombre:
Memoria - Ten Palomares, Maria.pdf
Tamaño:
4.3 MB
Formato:
Adobe Portable Document Format
Descripción:
Memoria