Navarro-Peris, E.; Álvarez-Piñeiro, L.; Schnabel, L.; Corberán, JM. (2021). Refrigerant maldistribution in brazed plate heat exchanger evaporators. Part B: Analysis of the influence of maldistribution on the evaporator performance. International Journal of Refrigeration. 131:312-321. https://doi.org/10.1016/j.ijrefrig.2021.04.003
Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/10251/181351
Título:
|
Refrigerant maldistribution in brazed plate heat exchanger evaporators. Part B: Analysis of the influence of maldistribution on the evaporator performance
|
Otro titulo:
|
Mauvaise distribution du frigorigène dans les évaporateurs d'échangeurs de chaleur à plaques Partie B: Analyse de l'influence de la mauvaise distribution sur les performances de l'évaporateur
|
Autor:
|
Navarro-Peris, Emilio
Álvarez-Piñeiro, Lucas
Schnabel, Lena
Corberán, José M.
|
Fecha difusión:
|
|
Resumen:
|
[EN] The maldistribution of the refrigerant mass flowrate among the different channels of a brazed plate heat exchanger evaporator with distributor, has been studied with a thermographic camera working under different ...[+]
[EN] The maldistribution of the refrigerant mass flowrate among the different channels of a brazed plate heat exchanger evaporator with distributor, has been studied with a thermographic camera working under different conditions of inlet vapor quality, superheat, and water temperature drop. Part A of this work includes the description of the experimental campaign and a full discussion of the obtained results. This paper (part B) presents, first an evaluation of the penalty caused by the refrigerant maldistribution on the evaporator performance, and the effect of the operation conditions on that penalty; second, a data reduction methodology, which allows the quantification of the maldistribution based on a series of simple assumptions and the flow conservation equations. Finally, given that it has been found that the water temperature drop across the evaporator has a strong influence on the performance penalty due to refrigerant maldistribution, the water temperature evolution is analyzed in detailed and the reasons for its great influence are explained and commented. On this regard, it is concluded that the penalty of the maldistribution on the evaporation performance strongly depends on the availability of the secondary fluid in the channels where most of the refrigerant liquid is concentrated. The described data reduction methodology, based on the analysis of the thermographies and the measured evaporator performance, is suitable to give an estimate of the maldistribution which seems reasonable and consistent with the observed data.
[-]
|
Palabras clave:
|
Brazed plate heat exchanger
,
Evaporator
,
Refrigerant maldistribution
,
Efficiency
,
Échangeur à plaques brasées
,
Évaporateur
,
Mauvaise distribution du frigorigène
,
Rendement
|
Derechos de uso:
|
Reconocimiento - No comercial - Sin obra derivada (by-nc-nd)
|
Fuente:
|
International Journal of Refrigeration. (issn:
0140-7007
)
|
DOI:
|
10.1016/j.ijrefrig.2021.04.003
|
Editorial:
|
Elsevier
|
Versión del editor:
|
https://doi.org/10.1016/j.ijrefrig.2021.04.003
|
Código del Proyecto:
|
info:eu-repo/grantAgreement/AEI/Plan Estatal de Investigación Científica y Técnica y de Innovación 2013-2016/ENE2017-83665-C2-1-P/ES/MAXIMIZACION DE LA EFICIENCIA Y MINIMIZACION DEL IMPACTO AMBIENTAL DE BOMBAS DE CALOR PARA LA DESCARBONIZACION DE LA CALEFACCION%2FACS EN LOS EDIFICIOS DE CONSUMO CASI NULO/
|
Agradecimientos:
|
The authors would like to acknowledge the Spanish 'Ministerio de Economia Y Competitividad', through the project "Maximizacion de la Eficiencia Y Minimizacion del Impacto Ambiental de Bombas de Calor Para la Descarbonizacion ...[+]
The authors would like to acknowledge the Spanish 'Ministerio de Economia Y Competitividad', through the project "Maximizacion de la Eficiencia Y Minimizacion del Impacto Ambiental de Bombas de Calor Para la Descarbonizacion de la Calefaccion/ACS en los Ed-ificios de Consumo Casi Nulo" with the reference ENE2017-83665-C2-1-P for the given support.
[-]
|
Tipo:
|
Artículo
|